§ 63.765. Glycol dehydration unit process vent standards.

924 words·~4 min read·/us/cfr/t40/s§ 63.765·

A research copy — for the controlling text, always check the official state or federal source. Not legal advice.

(a)This section applies to each glycol dehydration unit subject to this subpart that must be controlled for air emissions as specified in either paragraph (c)(1)(i) or paragraph (d)(1)(i) of § 63.764.
(b)Except as provided in paragraph
(c)of this section, an owner or operator of a glycol dehydration unit process vent shall comply with the requirements specified in paragraphs (b)(1) and (b)(2) of this section.
(1)For each glycol dehydration unit process vent, the owner or operator shall control air emissions by either paragraph (b)(1)(i), (ii), or
(iii)of this section.
(i)The owner or operator of a large glycol dehydration unit, as defined in § 63.761, shall connect the process vent to a control device or a combination of control devices through a closed-vent system. The closed-vent system shall be designed and operated in accordance with the requirements of § 63.771(c). The control device(s) shall be designed and operated in accordance with the requirements of § 63.771(d).
(ii)The owner or operator of a large glycol dehydration unit shall connect the process vent to a control device or combination of control devices through a closed-vent system and the outlet benzene emissions from the control device(s) shall be reduced to a level less than 0.90 megagrams per year. The closed-vent system shall be designed and operated in accordance with the requirements of § 63.771(c). The control device(s) shall be designed and operated in accordance with the requirements of § 63.771(d), except that the performance levels specified in § 63.771(d)(1)(i) and
(ii)do not apply.
(iii)You must limit BTEX emissions from each existing small glycol dehydration unit process vent, as defined in § 63.761, to the limit determined in Equation 1 of this section. You must limit BTEX emissions from each new small glycol dehydration unit process vent, as defined in § 63.761, to the limit determined in Equation 2 of this section. The limits determined using Equation 1 or Equation 2 must be met in accordance with one of the alternatives specified in paragraphs (b)(1)(iii)(A) through
(D)of this section. Equation 1 Where: ELBTEX = Unit-specific BTEX emission limit, megagrams per year; 3.28 × 10−4 = BTEX emission limit, grams BTEX/standard cubic meter-ppmv; Throughput = Annual average daily natural gas throughput, standard cubic meters per day. Ci,BTEX = average annual BTEX concentration of the natural gas at the inlet to the glycol dehydration unit, ppmv. Where: ELBTEX = Unit-specific BTEX emission limit, megagrams per year; 4.66 × 10−6 = BTEX emission limit, grams BTEX/standard cubic meter-ppmv; Throughput = Annual average daily natural gas throughput, standard cubic meters per day. Ci,BTEX = average annual BTEX concentration of the natural gas at the inlet to the glycol dehydration unit, ppmv.
(A)Connect the process vent to a control device or combination of control devices through a closed-vent system. The closed vent system shall be designed and operated in accordance with the requirements of § 63.771(c). The control device(s) shall be designed and operated in accordance with the requirements of § 63.771(f).
(B)Meet the emissions limit through process modifications in accordance with the requirements specified in § 63.771(e).
(C)Meet the emissions limit for each small glycol dehydration unit using a combination of process modifications and one or more control devices through the requirements specified in paragraphs (b)(1)(iii)(A) and
(B)of this section.
(D)Demonstrate that the emissions limit is met through actual uncontrolled operation of the small glycol dehydration unit. Document operational parameters in accordance with the requirements specified in § 63.771(e) and emissions in accordance with the requirements specified in § 63.772(b)(2).
(2)One or more safety devices that vent directly to the atmosphere may be used on the air emission control equipment installed to comply with paragraph (b)(1) of this section.
(c)As an alternative to the requirements of paragraph
(b)of this section, the owner or operator may comply with one of the requirements specified in paragraphs (c)(1) through
(3)of this section.
(1)The owner or operator shall control air emissions by connecting the process vent to a process natural gas line.
(2)The owner or operator shall demonstrate, to the Administrator's satisfaction, that the total HAP emissions to the atmosphere from the large glycol dehydration unit process vent are reduced by 95.0 percent through process modifications, or a combination of process modifications and one or more control devices, in accordance with the requirements specified in § 63.771(e).
(3)Control of HAP emissions from a GCG separator (flash tank) vent is not required if the owner or operator demonstrates, to the Administrator's satisfaction, that total emissions to the atmosphere from the glycol dehydration unit process vent are reduced by one of the levels specified in paragraph (c)(3)(i) through
(iv)of this section, through the installation and operation of controls as specified in paragraph (b)(1) of this section.
(i)For any large glycol dehydration unit, HAP emissions are reduced by 95.0 percent or more.
(ii)For any large glycol dehydration unit, benzene emissions are reduced to a level less than 0.90 megagrams per year.
(iii)For each existing small glycol dehydration unit, BTEX emissions are reduced to a level less than the limit calculated by Equation 1 of paragraph (b)(1)(iii) of this section.
(iv)For each new small glycol dehydration unit, BTEX emissions are reduced to a level less than the limit calculated by Equation 2 of paragraph (b)(1)(iii) of this section. [64 FR 32628, June 17, 1999, as amended at 66 FR 34551, June 29, 2001; 72 FR 38, Jan. 3, 2007; 77 FR 49570, Aug. 16, 2012]
Connections4 cite this
Cited by 4 sections · top 2
Citation graph
cites case law
§ 63.765
Glycol dehydration unit process vent standards.
Fed. Reg.×4
Cites 0Cited by 4 across 1 source
★   the supreme law of the land   ★
Don't Tread on Me
E Pluribus Unum — out of many, one

"If you don't know your rights, you don't have any."

Marginalia · a citizen's law index
A research desk, not legal advice. Always read the cited source before relying on a summary.
Questions or an issue? support@self-law.org
disclaimerMarginalia is a research index, not a law firm. Nothing on this site is legal, tax, or financial advice and no attorney–client relationship is formed by using it. Statutes, regulations, and case law change; summaries, search results, AI output, and member posts may be incomplete, out of date, or wrong. Any interpretation drawn from material on this site should be validated by a licensed attorney in your jurisdiction before you act on it.